ThingConnect

Digital I/O for old machines

How machines without a network-capable control join the same live dashboard as the rest of the fleet, and exactly what the connection can and can't see.

What digital I/O is

Digital I/O (digital inputs and outputs) means reading simple on/off electrical signals. Every machine, however old, has them: a run lamp that lights while the machine cuts, a relay that closes at the end of a cycle, an M-code output that pulses when a part is finished. A digital input reads whether each signal is on or off.

The 20-year-old machine that still holds tolerance deserves a place on the dashboard too. Digital I/O brings it into the same live view as the rest of the fleet, honestly labeled for what the connection can and cannot see.

  • Signal type

    In one line
    On / off, usually 24 V DC or a plain switch closure
  • Where it comes from

    In one line
    Signals the machine already has: lamps, relays, M-code outputs
  • Direction

    In one line
    Read-only. Nothing is written to the machine and no logic is changed
  • Best for

    In one line
    Machines whose control can't share data over a network

How an I/O connection works

  1. The machine

    • Run lamp / stack light
    • Cycle relay
    • Part-complete M-code
  2. Digital inputs

    on / off per signal

  3. ThingConnect gateway
  4. Running / stoppedCycle countsPart counts

A digital I/O connection taps those existing signals, read-only, at the terminals, and the gateway turns them into machine states and counts on the dashboard, exactly as it does for controller-connected machines.

  1. 1We find the signals on the machine that show running, cycle end and part complete.
  2. 2Each signal is checked: does it carry its own voltage (wet) or is it a plain switch (dry)?
  3. 3With the machine powered down, the signals are wired to matching digital inputs.
  4. 4The gateway turns each on/off change into states and counts, and we check them against the machine running real parts.

Which signals we tap

  • Run / cycle relay or lamp circuit

    What it yields
    Running vs stopped state, downtime events, utilization.
  • Cycle start / end pulse

    What it yields
    Cycle times and cycle counts.
  • Part-complete output (M-code / counter relay)

    What it yields
    Part counts for production tracking.
  • Alarm lamp (red stack light)

    What it yields
    That the machine is in alarm, without the alarm's name or number.

Wet and dry contacts

Before anything is wired, each signal is checked for what kind it is. Wiring a signal to the wrong input type either reads nothing or can damage the input.

Wet contactHas voltage

The signal carries its own voltage, for example a 24 V DC lamp or a PLC output. It is wired to an input that measures that voltage.

Dry contactPlain switch

A relay or switch that simply opens and closes, with no voltage of its own. The input supplies the voltage and reads whether the contact is closed.

Isolated inputs keep the machine's wiring electrically separate from the monitoring side, so a fault on one can't reach the other.

A practical example: the stack light

Many old machines have a stack light, the column of coloured lamps on top. Its lamps already show the machine's state, so tapping them gives a useful picture with very little wiring.

  • Green on

    Usually means
    Running a program
    Shown on the dashboard as
    Running
  • Amber on

    Usually means
    Waiting, idle or cycle finished
    Shown on the dashboard as
    Idle
  • Red on

    Usually means
    Alarm or emergency stop
    Shown on the dashboard as
    Alarm (without the alarm name)
  • All off

    Usually means
    Machine switched off
    Shown on the dashboard as
    Off

Lamp meanings vary by machine builder, so we confirm them on each machine before going live.

The honest limits

An I/O connection sees on/off, not meaning. It cannot tell why the machine stopped, which program was running, or whether an override is turned down: signals that exist only inside the control. Two consequences follow:

  • Operators supply the why.Stop reasons on I/O machines come from a two-tap operator prompt, not from alarm codes, so the reason list must be short and in the operators' own words.
  • OEE is partial. Availability and counts are solid; performance depth (override drift, in-cycle pauses) is not visible. We show what is measured and never estimate the rest into a prettier number.

Digital I/O compared with a controller connection

  • Running / stopped

    Digital I/O
    Yes
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    Yes
  • Cycle and part counts

    Digital I/O
    Yes, where a signal exists
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    Yes, from the control's own counter
  • Alarm state

    Digital I/O
    On / off only
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    Alarm number and message
  • Program running

    Digital I/O
    No
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    Yes
  • Feed and spindle overrides, spindle load

    Digital I/O
    No
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    Yes, depending on the control
  • Wiring at the machine

    Digital I/O
    Yes, at the signal terminals
    Controller connection (FOCAS, OPC UA, MTConnect, FTP)
    No, an Ethernet cable only

When to use digital I/O

  • Old control with no Ethernet or data interface

    Our recommendation
    Digital I/O
  • Control has Ethernet, but the data option isn't installed and adding it isn't worth it

    Our recommendation
    Digital I/O
  • Non-CNC equipment: presses, washers, manual machines

    Our recommendation
    Digital I/O
  • FANUC with Ethernet

    Our recommendation
    FOCAS
  • Newer control with OPC UA or MTConnect

    Our recommendation
    OPC UA or MTConnect

The right mix: on a typical Indian floor most machines carry network-capable controls and connect natively — FANUC over FOCAS above all — while the oldest few join over I/O. Be wary of any vendor proposing I/O boxes for a whole fleet whose controls could have spoken for themselves.

Is it safe for the machine?

  • Changing the machine

    How it's handled
    Monitoring doesn't change programs, settings or how the machine runs. Only existing signals are read.
  • Electrical safety

    How it's handled
    Wiring is done at the signal terminals with the machine powered down, and each signal is matched to the right input type.
  • Machine faults

    How it's handled
    Isolated inputs keep the machine's circuits separate from the monitoring side.

Frequently asked questions

Yes. Machines whose controls cannot speak over a network can still report run/idle state and count pulses through digital I/O signals — typically taken from existing relays, stack-light circuits, or spare M-code outputs. It is shallower than a controller connection, but it puts the whole fleet on one dashboard.

Reliably: running vs stopped, cycle start/end pulses, and a part-count signal where one exists. It cannot report alarms by name, program identity, override positions, or spindle load — those exist only inside the control. We label I/O-connected machines accordingly so nobody mistakes inferred data for controller truth.

No. The connection reads signals that already exist — a relay closing, a lamp circuit energizing, an M-code output pulsing. Nothing is written to the machine and no logic is changed. The wiring is done at the signal terminals, machine powered down, in under an hour per machine in most cases.

Almost never. If the control can speak — FANUC over FOCAS, or a machine with MTConnect or OPC UA — the native connection reads far more, with no wiring at all. I/O is the fallback for machines that have no other way in, not a shortcut for machines that do.

A wet contact carries its own voltage, such as a 24 V DC lamp or relay output. A dry contact is a plain switch closure with no voltage of its own; the input supplies it. Each needs the matching input type, which we check on every signal before wiring.

See it live

Mixed fleet, old and new? That's the normal case. See how the whole floor lands on one dashboard.